What is the maintenance requirement for EPSS circuit breakers for a Level I system?

EPSS circuit breakers for a Level I system, including main and feed breakers between the EPS and the transfer switch load terminals, shall be exercised annually with the EPS in the “OFF” position. (NFPA 110, 2010)

Additional Resource: NFPA 110